To use the RPS function, one of the alarm inputs must be designated as an
opening/closing channel (usually channel 4). The RPS output will activate when
an opening or closing signal is detected. It will de-activate when the opening or
closing signal has been acknowledged by the Alarm Receiving Centre. It is
allowable to have more than one input designated as an opening/closing channel,
but each must be acknowledged to de-activate the RPS output.
The RPS relay contacts (Normally Open, Common, Normally Closed) are available
for connection on terminal block TB4. To use this option, a warning device such
as a piezo bleeper or external strobe light should be connected as shown below.
The maximum current rating of the relay contacts is 1 Amp.
Line Fault Output
The Line Fault output is used to indicate, at the protected premises, that there is
a fault with the telephone line and/or communications with the redcare system
have been lost.
For stand alone units, the ‘Line Fault’ relay contacts (Normally Open, Common,
Normally Closed) are available for connection on TB4. The maximum current
rating of the relay contacts is 1.0 Amps.
For 3GSTU-PLI units, Line Fault connections are made automatically when it is
fitted into the host alarm panel. The host panel must be programmed to accept
this function.