assumed to have a REN value of 1.0 unless otherwise marked. If the STU is used
with an MCD, the combined REN will be 1½.
INSTALLATION
Training Courses
BT redcare offer a free training course for installers of the redcare service. For
further information call General Enquiries Tel: 0800 800 828
Pre-Installation Requirements
Before a STU installation can commence, a BT redcare Service Order must be
submitted to BT redcare by the Alarm Receiving Centre. This ensures that the
appropriate exchange connections have been made and a redcare block terminal
92A has been provided at the customer’s premises.
To enable an NVM to be programmed the following information is required:
a) The variant of STU is to be connected (-12V, -24V, -PLI, 11 zone or fire)
b) The alarm channels required and the function to be assigned to each
channel. The channels are typically assigned as follows:
For intruder alarm systems:
Channel 1 Fire Channel 5 Optional
Channel 2 Personal Attack Channel 6 Optional
Channel 3 Intruder Channel 7 Optional
Channel 4 Opening/Closing Channel 8 Engineer Test
For fire detection systems the fire stu has only three available channels
which can be used as required.
c) The polarity of the alarm inputs, positive applied or positive removed.
(Note: for a 3GSTU-PLI (plug-in) variant all alarm inputs must be positive
applied with the exception of alarm input 4 which must be positive
removed).
d) The type of line connection, PSTN (normal telephone line) or a Private
Wire (RedDIRECT)
e) The type of line monitoring function required